Application
1) The device (power cable, PTZ cable, video cable) of surveillance system
2) Bank surveillance system and housing district safety system
3) School, enterprise and road safety protection
Feature
1) Camera power, video cable, control cable multi stage protective circuit
2) International famous core component brand
3) High discharge current capacity, low insertion loss, superior transmission performance, no leakage current
4) Low residual voltage, perfect protective effect
5) Quick response, stable performance, reliable working
6) Small size, easy installation
Specification
Product model |
AJ3-220 |
1. power SPD specification |
Max continuous working voltage (Uc) |
220V AC |
Nominal discharge current (In) |
10KA |
Max discharge current (In) |
20KA |
Protection level |
≤100V |
2. signal SPD specification |
|
Video |
PTZ control |
Max continuous working voltage (Uc) |
12 |
24 |
Nominal discharge current (In) |
5KA |
Max discharge current (In) |
10KA |
Protection level |
≤25V(core wire—case/ground) |
Data transmission rate |
≤100Mbps |
Impedance |
75Ω |
Insertion loss |
≤0.5dB |
Interface type |
BNC-K/J |
RS485 |
3. other specification |
Case |
Aluminum material, oxidation surface(black, silver) |
Dimension |
110*61*28mm (including interface) |
Wire interface |
Power supply |
Compression joint port, suitable for 16-26AWG(0.15-1.3mm²) wire |
Video signal |
BNC connector |
Ground |
Earth wire terminal or 2.5mm²earth wire |
Installation |
Inside of box or cabinet |
Working conditions |
Temperature:-40~+85℃; Relative humidity:≤95%(25℃); Elevation≤3km |
Structure chart
Installation and wiring
1) According to protection demands, the SPD is connected by series between protected devices and signal path,
the closer the distance to protected devices, the better the protection effect.
2) To connect separately a)the cable to the input terminal of power, video and control port, b) output terminal
of SPD power, video and control to related interface of protected devices, c) ground line of SPD to earth wire
of lightning protection system
3) After wiring, please check it until everything is going well, to put into operation.
Product maintenance
1) The product does not need to be maintained specially, but to inspect at fixed period, especially before and
during thunderstorm season.
2) Once there is a failure during system operation, please remove the SPD device at first, if the system can
operate normally, the device is broken
Product standard
1) IEC61643-1:1998 Surge Protective devices connected to Low-voltage power;
2) Distribution system.Part1:Performance requirements and testing methods;
3) EN60950: Safety of information technology equipment, including electrical business equipment.
4) GB18802.1 low-voltage distribution system SP: performance demand and test method;
5) YD/T 1235.1 Communication Station low-voltage power system SPD technical requirement;
6) YD/T 1235.2 Communication Station low-voltage power system SPD test method; |